Heart of your home system
UniQube Heat Pump+ is special high energy efficiency package, as a solution for heating residential and industrial buildings, enabling reduction of cost of up to 75% per year and can operate at external air temperatures of -20°C. It contains UniQube central hot water storage tank, Heat Pump unit, digital controller Sorel XHCC.
UniQube Heat Pump+ is special high energy efficiency package, as a solution for heating residential and industrial buildings, enabling reduction of cost of up to 75% per year and can operate at external air temperatures of -20°C. It contains UniQube central hot water storage tank, Heat Pump unit, digital controller Sorel XHCC.
The tank inside is fully equipped model, combining functions of stratification, hygienic water heater, buffer, hydraulic separator, solar storage tank and solar support for the heating system.
UNIQUBE SQ-BPSW 440 HEAT PUMP+ | |||||||
---|---|---|---|---|---|---|---|
AERMEC ANK I - HX | 045 | 070 | 075 | 080 | |||
V/ph/Hz | 400V/3/50HZ | ||||||
12°C/7°C | Cooling capacity | (1) | kW | 12 | 14 | 16,7 | 18,9 |
Total input power | (1) | kW | 4,09 | 4,65 | 5,99 | 7,47 | |
EER | (1) | 2,93 | 3,01 | 2,79 | 2,53 | ||
ESEER | (1) | 4,79 | 4,65 | 4,65 | 4,59 | ||
Water flow rate | (1) | l/h | 2017 | 2375 | 2845 | 3222 | |
High static pressure | (1) | kPa | 61 | 81 | 61 | 4 | |
40°C/45°C | Heating capacity | (2) | kW | 12,11 | 15,1 | 17,5 | 20,05 |
Total input power | (2) | kW | 3,98 | 4,7 | 5,92 | 7,14 | |
COP | (2) | 3,04 | 3,21 | 2,96 | 2,81 | ||
Water flow rate | (2) | l/h | 2124 | 2633 | 3041 | 3471 | |
High static pressure | (2) | kPa | 60 | 70 | 50 | 27 | |
Performance under average climatic conditions (Average) UE n°811/2013 Pdesignh ≤ 70kW | |||||||
Pdesignh | (3) | 12 | 14 | 16 | 19 | ||
SCOP | (3) | 3,35 | 3,6 | 3,43 | 3,4 | ||
ηS | (3) | 131 | 141 | 134 | 133 | ||
Efficiency Energy Class | A+ | A+ | A+ | A+ | |||
Cooling mode for low temperature | |||||||
ηSC | 171,9 | 148 | 149,4 | 147,8 | |||
SEER | 4,37 | 3,78 | 3,81 | 3,77 |
UniQube SQ-BPSW | 310 | 440 | 800 | |
---|---|---|---|---|
D (diameter) | (mm) | 620 | 620 | 890 |
H1 (height) | (mm) | 1300 | 1730 | 1730 |
h (connectors) | (mm) | 1320 | 1750 | 1750 |
H (height) | (mm) | 1570 | 2000 | 2000 |
a (width) | (mm) | 725 | 725 | 960 |
Pivot measurement | (mm) | 1730 | 2130 | 2219 |
Net tank capacity | (l) | 290 | 413 | 773 |
Approx. weight | (kg) | 104 | 130 | 160 |
Connections C, E, I, J | 5/4" | |||
Max. working temp. | (°C) | 90 | ||
Max. working pressure | (bar) | 6 | ||
Max. test pressure | (bar) | 9 | ||
S2 Solar sensor position | (mm) | 1110 | 1550 | 1550 |
S3 DHW sensor position | (mm) | 600 | 900 | 900 |
S4 Heating sensor position | (mm) | 140 | 140 | 140 |
S5 Overheating protection | (mm) | 140 | 140 | 140 |
Nominal flow rate (all exchangers) | (l/min) | 20 | ||
Max. flow rate (all exchangers) | (l/min) | 30 | ||
Max. working pressure (all exchangers) | (bar) | 10 | ||
Max. test pressure (all exchangers) | (bar) | 15 | ||
Solar Heat Exchanger | ||||
Connections F, G | 5/4" | |||
Capacity | (l) | 2,85 | 4,12 | 4,12 |
Output area | (m²) | 1,05 | 1,43 | 1,43 |
DHW Heat Exchanger | ||||
Connections A, B | 5/4" | |||
Capacity | (l) | 16,15 | 21,86 | 21,86 |
Output area | (m²) | 5,06 | 6,78 | 6,78 |
Dedication of our expert team have already contributed the implementation of quality standards ISO 9001:2008 and certification of the UniQubes, by TUV Hessen, for complying with Pressure Equipment Directive